Kentucky Legionella Compliance & Water Quality Standards
Executive Overview
Kentucky CHFS enforces water safety standards under 902 KAR 20:016, mandating risk management plans and monitoring protocols.
Governing Public Health Agency & Reporting Mandates
- Agency Name: Kentucky Cabinet for Health and Family Services (CHFS)
- Infectious Disease Reporting Hotline: (888) 973-7678 (Kentucky Reportable Disease Hotline)
- Main Contact Phone: (502) 564-3970
- Official Portal: https://chfs.ky.gov
- Mandatory Reporting Window: All diagnosed cases of Legionellosis (Legionnaires' disease / Pontiac fever) must be reported to Kentucky Cabinet for Health and Family Services (CHFS) within 24 hours.
Statutory & Regulatory Citations
- 902 KAR 20:016: Hospitals - Operations and Services Standards (Kentucky Cabinet for Health and Family Services) — Enforced via State Licensing Inspection
Regional Water Chemistry & Disinfection Profile
- Dominant Municipal Disinfectant:
FREE CHLORINE - Typical Distribution Residual: 0.5 – 2 mg/L (ppm)
- Average Water Hardness: 8 GPG (137 mg/L CaCO₃) — Classified as MODERATE
- Calculated Scaling Risk: MODERATE
- pH Operating Range: 7.2 – 7.9
- Regional Water Contaminants / Vectors: Ohio River basin organics, Karst limestone mineral deposits
Mandatory Environmental Testing Cadence
| System Type | Facility Scope | Frequency | Required Test Method | Compliance Notes |
|---|---|---|---|---|
| Domestic Hot | healthcare | Quarterly_90d | CDC ELITE Culture ISO11731 | Quarterly surveillance in acute and long-term care. |
Action Thresholds & CAPA Containment Protocols
Potable Water — Level 3 Critical Emergency (10+ CFU/mL)
- Mandatory Containment Protocol:
- Notify Kentucky CHFS within 24 hours.
- Clearance Verification Retest: Within 7 days.
- Mandatory Public Health Notification: Within 24 hours.
Surveyor & CMS Audit Defense Checklist
- Active ASHRAE 188 Water Management Plan (WMP) updated within the last 12 months.
- Water Safety Team Charter with designated Infection Prevention, Facilities, and Clinical leads.
- Process Flow Diagrams (PFDs) identifying point-of-entry, booster pumps, calorifiers, and distal sample locations.
- Daily / Weekly Physical & Chemical Monitoring Logs (temperature and disinfectant residual).
- Closed-Loop Corrective Action Logs (CAPA) documenting immediate remediation for any out-of-spec reading.