Thermal Line Flush & High-Temperature Disinfection
Comprehensive field protocol for elevated hot water thermal pasteurization and physical disinfection across domestic hot water heaters, recirculation loops, and terminal point-of-use fixtures.
Automate Your Facility's Stagnation & Flushing Logs
WaterShield links this exact SOP directly to technician mobile rounds, QR capture points, and closed-loop CAPA workflows with SHA-256 Merkle root verification.
1. Required Personal Protective Equipment (PPE)
Mandatory Scald & Thermal Splash Protection
2. Step-by-Step Thermal Disinfection Execution
Sequential 5-Step Protocol per ASHRAE Guideline 12-2020 §8
3. Verification Criteria & Thermal Lethality Kinetics
Temperature vs. Kill Time for Legionella pneumophila
SOP-TH-01 Official Verification Standard
Terminal water temperature >= 122.0°F (50.0°C) after 5-minute continuous flush. If the terminal water fails to sustain this threshold, the fixture must be re-isolated, heater capacity investigated, and a corrective engineering review initiated in the QMS CAPA logbook.