CMS Tag F-880 vs. CMS Tag F-689 · ASSE 1070

Resident Scald Prevention vs. Legionella TMV Balance Calculator

Prove your Assisted Living or Skilled Nursing Facility holds central DHW storage at ≥140°F and recirculation return at ≥124°F (CMS F-880) while delivering safe 110°F–115°F tempered water to resident fixtures via ASSE 1070 mixing valves (CMS F-689). Print or export a 1-page surveyor-ready TMV log in one click.

Water System Thermal Inputs
Model central water heater storage, recirculation return, and ASSE 1070 mixing valve discharge temperatures.
140°F
100°F (Growth Zone)Target: ≥140°F (F-880)160°F
124°F
90°FTarget: ≥124°F (ASHRAE 188)150°F
112°F
95°FSafe: 110°F–115°F (F-689)≥120°F Scald
60°F
40°F (Winter)Target: ≤68°F80°F (Warm Climate)
Dual CMS Survey Verdict (F-880 vs. F-689)

Compliant Dual-Zone

Dual-zone thermal barrier verified. Maintain weekly Sentinel 3 boiler/recirc checks and quarterly ASSE 1070 TMV calibration logs.

CMS Tag F-880
COMPLIANT
Legionella Thermal Control
Central DHW storage (140°F ≥ 140°F) and recirculation return (124°F ≥ 124°F) suppress Legionella colonization.
CMS Tag F-689
COMPLIANT
Resident Scald Prevention
Resident tap discharge (112°F) sits within the 110°F–115°F ASSE 1070 elder-care safe zone for CMS Tag F-689 compliance.
Frail Elderly 3rd-Degree Burn
> 10 minutes
Adult skin: > 30 minutes
TMV Hot / Cold Blend
81.3% / 18.7%
Normal ASSE 1070 mixing balance.
Pre-Fill Senior Living WMP
CMS Tag F-880 & F-689 Survey Verification Sheet
1-Page ASSE 1070 TMV Calibration & Thermal Verification Log
Facility: Assisted Living & Memory Care Community · DHW Storage: 140°F · Recirc Return: 124°F · Verdict: Compliant Dual-Zone
Target: 110°F–115°F Tap / ≥140°F Boiler
Valve IDLocation / WingStandardHot InletCold InletDischargeStatusTech Initials & Date
TMV-MASTER-01Central Boiler Room — Master Distribution HeaderASSE 1017140°F60°F124°FPASS_________________
TMV-WING-AWing A Resident Suites — Mixing Valve StationASSE 1070124°F60°F112°FPASS_________________
TMV-WING-BWing B Memory Care — Mixing Valve StationASSE 1070124°F60°F112°FPASS_________________
TMV-SPA-101Therapeutic Bath / Whirlpool Suite 101ASSE 1070124°F60°F112°FPASS_________________
References: CMS 42 CFR §483.80 (Tag F-880), 42 CFR §483.25(d) (Tag F-689), ASHRAE 188, ASSE 1070, Moritz & Henriques Burn Curve.
Maintenance Director Sign-Off: ______________________